Question
I'm interested in finding out more about electronic relative humidity sensors used in dry kilns. Exposure to the acidic, high humidity, high temperature environment of a dry kiln is always an issue with these types of sensors.
Forum Responses
I do not believe that anyone makes RH sensors that will stand up to normal kiln temperatures and humidities. Lignomat does make an EMC sensor (looks like a white piece of blotter paper) that is widely used. Brunner also has a similar style sensor.
Gene Wengert, forum technical advisor
The only two problems with DB/WB sensors is getting the water to them all the time and getting enough airflow. I have suggested putting a small fan on the WB sensor. Turn it on and off and watch the reading change depending on whether the fan is on or off. Often the entire kiln runs better with adequate air across the WB!
Gene Wengert, forum technical advisor
a) No one seems to definitively know which ones really work and which ones don't for this particular application.
b) The ones that are being used aren't reliable and/or accurate in some key situations like low RH or high RH conditions.
c) Other varieties being used (cellulose-based) are known to have problems related to long-term exposure to the harsh industrial environment of a kiln.
d) At the end of the day, it's best to buy a cheapy that's hand-held and the solution is to keep your hand stuck inside the kiln for the duration of the schedule and record the numbers with your free hand.
Sounds like a good research project in the making. When one does a Google search on RH sensors, there appears to be a whole swack of them out there. It would be nice to throw a half dozen different ones into a red oak kiln over a year, and see which really work after 12 months. I'm surprised this hasn't been done yet.
We have used three different brands. The first was Ohmico. It was an import from Europe. It drifts but is easy to calibrate. The second is from Elan Technology. It's stable and, if it becomes contaminated, you rinse it off with distilled water. The third is from Rotronics. I like it because it is very stable and the sensor is well protected inside a teflon filter.
Wet bulb measurement is often very inaccurate. When the air is blowing over the top of a charge and hits the WB in the back, the controller might respond to the dry air by spraying. When the air is going through the charge and then to the WB, the controller responds by venting. That's why you see an oscillation in DB in one fan direction. So we use two transmitters. One on either side of the charge.
Accuracy is typically +/-2% from 10 to 100% RH. Look at your EMC chart in the DKOM and you'll see that a wet bulb can't come near this accuracy.
Temperature operating range is up to 160. After 160, accuracy isn't guaranteed. Above 160, what difference does a little inaccuracy make?
If you find an accurate portable meter for $29, go buy a lottery ticket. It's your lucky day.
Today we installed four in two new kilns for a customer that has around 20 or 30 of them.
Your comment about WB being inaccurate is wrong. They actually are the basis for humidity measurement and have been since 1909. Regarding the EMC, the chart in the handbooks is for 1 F increments; if you need closer values (but in kiln drying we do not), there is a formula that you can use to get more precise. But, note that RH to EMC conversions are equally inaccurate. The WB/DB is the most accurate basis for EMC and RH measurement that ordinary people have available.
You also seem to imply that the WB temperature varies through a kiln load. This is not true, unless there is heating inside the load. Hence, only one WB sensor is needed in a kiln (unless the kiln is long). The DB, EMC and RH does vary from side to side, but not WB. That is why you have to use two sensors.
The literature for every RH sensor I have looked at for use in dry kilns has a statement that it is not to be used in acidic atmospheres. Apparently you have found two or three that do not have this restriction.
Gene Wengert, forum technical advisor
Does anybody see their DB fluctuate in one fan direction but not the other?
It sounds like there are many problems present. Is there any baffling on top of the stack? There should be.
How dry the air is because it does not go through the stack does not change the wet-bulb reading - it stays the same from the point of entering the stack to leaving the stack. Is there enough water present at the wet bulb wick or is it exposed to the heating coil? Both of which would be interpreted by the controller that the air is dry.
The dry bulb should not be oscillating within one direction of airflow. It should oscillate as the air direction is changed. If it does oscillate within one direction something is wrong and a close inspection of the operation is needed. (In other words, I can not think of a reason from this distance.)
Bad WB readings are the result of bad operation of the WB--not enough water, too hot water, poor air flow, poor wick, etc.
The wet-bulb reading (not the actual WB value, but the indication on an instrument) will vary due to different airflow across the bulb in the two fan directions. Often, when the air is going upward in the plenum, the flow across the wick is poorer than when the air is going downward. Also, there is one kiln design that has the vent fairly close to the wet-bulb, so that the cold vent air affects the WB reading when the fans blow in one direction. In this case, any sensor would be affected.
Dry-bulb temperatures can fluctuate in one direction because of the plenum size, vent locations (and poor mixing of the vent air with the kiln air), heating coils that are not balanced (trap on each one) so that one bank heats more quickly than the other, direct exposure to heating coil radiation (IR radiation), or poor sensor location. Perhaps there are other reasons, too.
A related problem occurs with two DB sensors that are switched on and off (reversed) when the fans reverse. Such reversing of the sensors is done with a relay and often the contacts wear. With resistance sensors, we are dealing with very small resistance differences being large temperature differences. In computer systems, the sensors are not switched, but the ones that the computer uses for control (the active sensors) will be switched. In this case, there is no relay switching; the data are switched in the computer.
In older control systems, whenever there are questionable and strange readings, the first question is whether it is the sensor giving a false reading or if it is actually the air temperature that is changing.
Back to WB readings, the theory (thermodynamics) of the WB is well described mathematically (Byrd, Stewart and Lightfoot). In this text, the affect of velocity is also described. At approximately 600 fpm across the bulb, changes in velocity have little affect. However, if you get under 400 fpm, variations in velocity produce variations in cooling. Another important factor is the temperature of the water--it cannot be too cold or too hot. This is especially critical in units with large water boxes. Also, the WB data is based on a muslin wick. Some of the wicks used today are not as absorptive as they should be. In fact, I encourage everyone to wash their wicks once (no soap) to rinse out the sizing used in many fabrics. Sizing makes your new shirt look like a new shirt to everyone else, but interferes with evaporation!
Gene Wengert, forum technical advisor
If the sensor is not positioned where it receives the air coming out of the stack before it is affected by other factors, then the reading is in error.
So, no matter which way the air is flowing, the total energy is the same and the wet-bulb is constant.
The key is ENERGY and not HEAT--or hot air, cooled air, or vaporization heat. Adiabatic processes are concerned about ENERGY, in any form. Perhaps this idea will help your understanding.
Gene Wengert, forum technical advisor
The key is that energy is not used or disposed of in the lumber stack. All the energy going in or coming out is accounted for within the stack of lumber.
Gene Wengert, forum technical advisor
I have in front of me charts from when I considered this question a couple years ago. The charts note 5/4 cherry. One chart shows a six to eight percent shift in RH when the fans change direction for about the first three days. Then the difference when fans change is minimal. The difference recorded could have been the difference in transmitters. This is the point where minimal energy is left behind in the stack. It stays this way until the last four or five days when the RH again starts shifting up and down with the fans changing direction. It was about a 6% shift downward when the DB was 130 and the fans reversed.
If your sensors are removable, switch them with each other. Now see if the humid side has also changed. Also, I have seen one kiln where the RH was a calculated value (the sensor did not adjust for temperature in itself, but relied on the computer to do it) and the programmer forgot to change the DB used in the calculation for the sensor. This gave a false DB in one direction, but not the other. This is also a problem with DB/WB sensors that report or record depression and EMC or RH, rather than just the temperatures.
Gene Wengert, forum technical advisor
Gene Wengert, forum technical advisor
If we were talking about a conventional kiln operating in a cold climate, you might think of the door as a big condenser to make it easier to understand what's going on thermodynamically.
Total accuracy is a moot point anyway. We replaced the control system on a NYLE last week. The wet bulb RTD was in a wick stained brown. The RTD was almost in a water box crusted with corrosion and filled with warm water. The operator had learned to deal with it. The new controller uses one RH transmitter.
Comment from contributor A:
I've dried lumber for 20 years in steam kilns, direct-fired kilns, slope grate green fueled kilns, fluidized bed kilns. I have used one control system that has worked with every one of them except the fluidized bed, which did not have it installed. I use a RH derivitive system developed by drying technologies as the primary shutdown parameter. I also have the new Accudry system installed on one of my kilns. Beleive me, the RH method works more consistently than any other. I have Delta T, wet bulb drop, RH, wet bulb set point and max time as choices. The RH is based on a chart using wet bulb/dry bulb ratios. Like I said, I am not a professor or engineer, but I dry lumber every day of the week.